FPU-75A Rack Mounted

point.png Fast response - Full response time ≤ 5ms

point.png Excellent filtering performance - Simultaneously filter out 2~50 harmonics

point.png Significant  filtering effect - Single harmonics filtering rate ≥98%, comprehensive harmonic filtering rate ≥97%




 Technical Parameters

System parameter

Grid voltage400V/690V (-40%, +20%)
Rated frequency50/60±5%Hz
Wiring systemThree-phase three-wire/Three-phase four-wire
Circuit topologyThree-level



Performance index

Rated current75A
Compensation modeImplementing Harmonics, reactive power ,Any combination of imbalance compensation
Harmonic compensation capability2 ~ 50th harmonic compensation, eliminate all or selected harmonics
Harmonic order settingIndividual setting of each harmonic
Harmonic compensation efficiencyGreater than 97%
Reactive power compensationCapacitive full range reactive power compensation
Three-phase unbalance compensationHave
Full response time≤5ms
Machine efficiency>97%
Parallel operation capabilitySupports up to 10 modules in parallel
CT parametersPrimary side current 100 ~ 10000A, secondary current 5A (1A optional)
CT positionLoad side or power side
Protection methodGrid over and under voltage, grid over and under frequency, input voltage reverse order, over current, over heat,overload automatic current limit protection, bus short circuit
cooling methodIntelligent air cooling, automatic adjustment of air volume according to heat dissipation conditions and load 
noise≤65dB



Communication and monitoring

ProtocolModbus protocol
Communication InterfacRS485/RS232 /Ethernet (optional)
Monitoring module2.8 Inch LCD screen
Display contentReal-time running information such as voltage, current, frequency, power factor, waveform curve, parameter setting, record query, etc.



Mechanical properties

IP ratingIP20 (others can be customized)
Dimensionrefer to mechanical characteristics for details
Weightrefer to mechanical characteristics for details
ColorRAL7035



Environmental requirements

Operating temperature-25℃~+50℃, derating above 40 ℃
Relative humidity5%~95%, no frost
Relative humidity2000m, exceeding derating operation



Related qualifications

CertificationCQC certification, type test report



 Download