Central Inverter

EP-6250-HA-UD/10~35

MV Turnkey Solution for 1500V Utility PV Plant

  • --EP-6250-HA-UD10~353.png
  • --EP-6250-HA-UD10~352.png
  • --EP-6250-HA-UD10~351.png
  • --EP-6250-HA-UD10~353.png
  • --EP-6250-HA-UD10~352.png
  • --EP-6250-HA-UD10~351.png
  • Features

  • Input (DC)

  • Output (AC)

  • Protection

  • Efficiency

  • Transformer

  • General Data

  • Features

  • Input (DC)

  • Output (AC)

  • Protection

  • Efficiency

  • Transformer

  • General Data

Features
  • f2icon04.svg
    More power generation

    · Inverter Max. efficiency 99%, Euro efficiency 98.7%
    · 1500Vdc PV system reduce power loss
    · High DC/AC ratio up to 1.8

  • f2icon05-771.svg
    Low system cost

    · Convenient for large block size PV plant
    · Integrated MV transformer and switchgear
    · Night SVG function optional

  • f2icon06923-169.svg
    High reliability

    · Capacitor life prediction technology
    · Key components at front side, easy for maintenance
    · Current sensor for each DC input, more reliable for monitoring and control

  • f2icon07.svg
    Grid friendly

    · Adjustable reactive power
    · Low harmonics and fast response for grid regulation

Input (DC)
ModelEP-6250-HA-UD/10~35
Max. PV input voltage1500V
Max. input current4110A*2
MPPT voltage range for nominal power900~1300V
Number of MPPT trackers4
Max. Number of DC inputs22
Output (AC)
ModelEP-6250-HA-UD/10~35
AC output power2*3125kVA@50℃/2*3625kVA@30℃
AC voltage range10~35kV
Rated grid frequency/range50 Hz/45~55 Hz, 60Hz/55~65 Hz
Output current harmonic(at nominal power)<3%
DC current injection< 0.5% In
Power factor at nominal power/range>0.99/0.8 lagging to 0.8 leading
Protection
ModelEP-6250-HA-UD/10~35
DC input protectionLoad break switch+fuse
AC output protectionCircuit breaker
AC MV output protectionCircuit breaker
Over-voltage protectionDC Type II/AC Type II
Leakage current monitoringYes
Grid monitoring/Ground fault monitoringYes/Yes
Insulation monitoringYes
Overheat protectionYes
Night SVG functionOptional
Anti-PID functionOptional
Efficiency
ModelEP-6250-HA-UD/10~35
Max. efficiency99.00%
EU efficiency98.70%
Transformer
ModelEP-6250-HA-UD/10~35
Transformer rated power6250kVA
Transformer max. power7250kVA
LV/MV Voltage0.63-0.63/10~35kV
Transformer VectorDy11y11
Transformer cooling typeONAN (Oil Natural Air Natural)
General Data
ModelEP-6250-HA-UD/10~35
Auxiliary power supplyStandard: 5kVA, Optional: Max. 40kVA
Protection levelInverter: IP65, Others: IP54
Temperature-30~+ 60℃
Allowed humidity(non condensing)0 ~ 95 %
Cooling methodTemperature controlled forced air cooling
Max.operating altitude2000m (standard) />2000m (optional)
DisplayTouch screen
Communication portRS485/Ethernet, Optional: optical fiber
Certificates and approvals (more available on request)CE,IEC 62109, IEC 61727, IEC 61683, IEC 62116, IEC 60068, IEC61000,IEC60076,IEC62271
Dimension(W*H*D)12192×2896×2438mm
Weight28t